Technical Data
Describe
Circulating rubber, elastic closed cell structure
Characteristic
Insulation
Weighting
50-70 kg/m3
Color
Black
Thickness
6mm
Absorbing sound
35dB (A)
Permeability resistance coefficient
µ > 7,000
Thermal conductivity coefficient
0.036 - 0.04 W/m.K
Water absorption coefficient
0.9% by volume (after 28 days)
Limited Oxygen Index
Minimum 35%
Operating temperature
-40°C to +105°C
-40°C to +105°C
15mm x 6mm x 15m / 20mm x 6mm x 15m / 40mm x 6mm x 15m
Longevity
12 months when stored in an enclosed container
BS 476 Part 6 - Fire Propagation
Class 0
BS 476 Part 7 - Surface Spread of Flames
Class 1
BS 476 Part 24 và ISO 6944
Up to 4 hours in terms of stability, integrity and insulation when roong is used between the flanges of the windpipe (BS 476 Part 24 và ISO 6944)
Advantages
The advantages of Flamebar Fire Retardant Gasket are:
- Self-adhesive with easy-to-peel finger lift use.
- It will not shrink or degrade in normal use.
- Unaffected by water or moisture.
- Maintainance free.
Installation
- Simply remove the backing paper by peeling it off as the gasket unwinds.
- To position apply the gasket to one surface and locate and fix flanges together.
Compliance
Flamebar Fire Retardant Gasket is manufactured in the EU, meeting the highest quality control standards in compliance with ISO EN 9002.
Storage and Handling
Flamebar Fire Retardant Gasket should be stored in dry, cool conditions. Shelf life is 12 months.